
Application Code | III
|
Type Version | IDC
|
Lamp Type | TL-D/PL-L
|
Number of Lamps | 1
piece/unit
|
Number of Products on MCB (16A Type B) (Nom) | 28
|
Automatic Restart | Yes
|
Input Voltage | 220 to 240
V
|
Input Frequency | 50 to 60
Hz
|
Operating Frequency (Nom) | 45
kHz
|
Ignition Method | Programmed Start
|
Crestfactor (Max) | 1.7
|
Power Factor 100% Load (Nom) | 0.99
|
Ignition Time (Max) | 0.9
s
|
Mains Voltage Performance (AC) | -8%-+6%
|
Mains Voltage Safety (AC) | -10%-+10%
|
Earth Leakage Current (Nom) | 0.5
mA
|
Inrush Current Width | 0.25
ms
|
Constant Wattage Deviation | -2%/+2%
|
Ballast Factor (Nom) | 0.95
|
Power Factor (Nom) | 0.99
|
Power Losses (Nom) | 4.3-4.4
W
|
Inrush Current Peak (Max) | 18
A
|
Efficiency at full load [%] | 93.3
%
|
Connector Type Input Terminals | WAGO 251 universal connector
[ Suitable for both automatic wiring (ALF and ADS) and manual wiring] |
Cable Capacity Output Wires Mutual (Nom) | 200
pF
|
Connector Type Output Terminals | WAGO 251 universal connector
[ Suitable for both automatic wiring (ALF and ADS) and manual wiring] |
Cable Length Hot Wiring | 0.75
m
|
Wire Striplength | 8.0-9.0
mm
|
Dual Fixture Master/Slave | Not applicable
[ Master/Slave oper. not applicable] |
Input Terminal Cross Section | 0.50-1.00
mm²
|
Output Terminal Cross Section | 0.50-1.00
mm²
|
Cable Capacity Output Wires to Earth (Nom) | 200
pF
|
Rated Ballast-Lamp Power | 58 W
|
Rated Lamp Power on TL-D | 58
W
|
System Power on TL-D | 56.3W@58W; 63.8W@70
W
|
Lamp Power on TL-D | 51.9W@58W; 59.6W@70
W
|
Power Loss on TL-D | 4.4W@58W; 4.3W@70
W
|
System Power on PL-L | 55.8W@55
W
|
Lamp Power on PL-L | 51.5W@55
W
|
Power Loss on PL-L | 4.3W@55
W
|
T-Ambient (Max) | 60
°C
|
T-Ambient (Min) | -25
°C
|
T-Storage (Range) | -40 °C to 50 °C
|
T-Storage (Max) | 50
°C
|
T-Storage (Min) | -40
°C
|
T-Case Lifetime (Nom) | 80
°C
|
T-Case Maximum (Max) | 80
°C
|
T-Ignition (Max) | 60
°C
|
T-Ignition (Min) | -25
°C
|
Housing | L 280x30x28
|
Nominal Light Output After 60 Seconds | 100% of EBLF
|
Battery Voltage Lamp Ignition | 186-275
V
|
Normal Operating Voltage (DC) | 220-240
V
|
Battery Voltage Lamp Operation | 186-275
|
Battery Voltage Guaranteed Operation | 176-275
V
|
Battery Voltage Guaranteed Ignition | 186-275
V
|
Emergency Ballast Lumen Factor (EBLF) (Nom) | 100
%
|
Nominal Light Output After 5 Seconds | 50% of EBLF
|
Energy Efficiency Index | A2 BAT
|
||
IP Classification | IP20
[ Finger-protected] |
||
EMI 9 kHz ... 30 MHz | EN55015
|
||
EMI 30 MHz ... 1000 MHz | EN55022 level B
|
||
Safety Standard | IEC 61347-2-3
|
||
Performance Standard | IEC 60929
|
||
Quality Standard | ISO 9000:2000
|
||
Environmental Standard | ISO 14001
|
||
Harmonic Current Emission Standard | IEC 61000-3-2
|
||
EMC Immunity Standard | IEC 61547
|
||
Vibration Standard | IEC68-2-6 F c
|
||
Bumps Standard | IEC 68-2-29 Eb
|
||
Humidity Standard | EN 61347-2-3 clause 11
|
||
Approval Marks | CE marking
|
ENEC certificate
|
VDE-EMV certificate
|
Temperature Marking | Yes
|
||
Emergency Standard | IEC 60598-2-22
|
||
Hum And Noise Level | < 30 dB(A)
|
Ambient temperature range | -25 °C to 60 °C
|
Full product code | 872790091170100
|
Order product name | HF-P 158 TL-D III 220-240V 50/60Hz IDC
|
EAN/UPC - Product | 8711500999702
|
Order code | 913713031866
|
Numerator - Quantity Per Pack | 1
|
Numerator - Packs per outer box | 12
|
Material Nr. (12NC) | 913713031866
|
Net Weight (Piece) | 0.205
kg
|