HF-Selectalume II HT for TL5/TL-D lamps

HF-S 249 TL5 II HT 220-240V 50/60Hz

HF-S 249 TL5 II HT 220-240V 50/60Hz

  • Affordable solution designed for high resistance

    Product information

    Downloads

    Leaflet
    Size:400.4 kB

    See all downloads

Videos

[trigger to render Video Gallery]

Images

Specifications Show all

General Information
Application Code
II HT
Type Version
mk1
Lamp Type
TL5
Number Of Lamps
2 piece/unit
Number Of Products On MCB (16A Type B) (Nom)
12
Automatic Restart
Yes
Operating and Electrical
Input Voltage
220 to 240 V
Input Frequency
50 to 60 Hz
Operating Frequency (Nom)
42 kHz
Crestfactor (Nom)
1.7
Power Factor 100% Load (Nom)
0.99
Preheat Time
0.93 s
Mains Voltage Performance (AC)
202-254V-8%-+6%
Mains Voltage Safety (AC)
198-264V-10%-+10%
Earth Leakage Current (Max)
0.5 mA
Inrush Current Width
0.35 ms
Ballast Factor (Nom)
1
Power Losses (Nom)
6 W
Inrush Current Peak (Max)
31 A
Wiring
Connector Type Input Terminals
WAGO 251 universal connector  [ Suitable for both automatic wiring (ALF and ADS) and manual wiring]
Cable Capacity Output Wires Mutual (Max)
200 pF
Connector Type Output Terminals
WAGO 251 universal connector  [ Suitable for both automatic wiring (ALF and ADS) and manual wiring]
Cable Length Hot Wiring
0.75 m
Wire Striplength
8.0-9.0 mm
Dual Fixture Master/Slave
Possible, lamp wires 2m max. length  [ Master/Slave operation possible]
Input Terminal Cross Section
0.50-1.50 mm²
Output Terminal Cross Section
0.50-1.50 mm²
Cable Capacity Cold Output Wires - Earth (Max)
200 pF
Cable Capacity Hot Output Wires - Earth (Max)
200 pF
System characteristics
Rated Ballast-Lamp Power
49 W
Lamp Power On TL5 HT
104 W
Rated Lamp Power On TL5 HT
49 W
System Power On TL5 HT
110 W
Power Loss On TL5 HT
6 W
Temperature
T-Ambient (Max)
60 °C
T-Ambient (Min)
-25 °C
T-Storage (Max)
50 °C
T-Storage (Min)
-40 °C
T-Case Lifetime (Nom)
80 °C
T-Case Maximum (Max)
80 °C
Mechanical and Housing
Housing
L 360x30x21
Emergency Operation
Nominal Light Output After 60 Seconds
100% of EBLF
Normal Operating Voltage (DC)
220-240 V
Battery Voltage Guaranteed Operation
176-275 V
Battery Voltage Guaranteed Ignition
186-275 V
Emergency Ballast Lumen Factor (EBLF) (Nom)
0.7 %
Nominal Light Output After 5 Seconds
50% of EBLF
Approval and Application
Energy Efficiency Index
A2 BAT
EMI 9 kHz ... 30 MHz
EN55015
Vibration Standard
IEC68-2-6 F c
Bumps Standard
IEC 68-2-29 Eb
Approval Marks
EMC
F-Marking
CE marking
ENEC certificate
CCC certificate
C-Tick certificate
TISI marking
SIRIM approval
CB Certificate
VDE-EMC marking
CCC certificate
Hum And Noise Level
< 30 dB(A)
Product Data
Full product code
871829166779700
Order product name
HF-S 249 TL5 II HT 220-240V 50/60Hz
EAN/UPC - Product
8718291667797
Order code
913700690166
Numerator - Quantity Per Pack
1
Numerator - Packs per outer box
12
Material Nr. (12NC)
913700690166
Net Weight (Piece)
0.280 kg
Installation Diagrams
2 Lamps HT
2 Lamps HT