HF-Performer II Xtreme for TL5/TL-D lamps

HF-P Xt 236 TL-D EII 220-240V 50/60Hz

HF-P Xt 236 TL-D EII 220-240V 50/60Hz

  • Xtreme drivers for long life and reliable performance

    Product information

    Downloads

    Leaflet
    Size:256.7 kB

    See all downloads

Videos

[trigger to render Video Gallery]

Images

Specifications Show all

General Information
Application Code
EII
Type Version
mk1
Lamp Type
TL-D
Number Of Lamps
2 piece/unit
Number Of Products On MCB (16A Type B) (Nom)
12
Automatic Restart
Yes
Operating and Electrical
Input Voltage
220 to 240 V
Input Frequency
50 to 60 Hz
Operating Frequency (Min)
42 kHz
Ignition Method
Warm Start
Crestfactor (Max)
1.7
Power Factor 100% Load (Nom)
0.96
Ignition Time (Max)
2.0 s
Mains Voltage Performance (AC)
-8%-+6%
Mains Voltage Safety (AC)
-10%-+10%
Earth Leakage Current (Nom)
0.5 mA
Inrush Current Width
0.350 ms
Constant Wattage Deviation
-2%/+2%
Ballast Factor (Nom)
1.0
Power Losses (Nom)
8.0 W
Inrush Current Peak (Max)
31 A
Wiring
Connector Type Input Terminals
WAGO 251 universal connector  [ Suitable for both automatic wiring (ALF and ADS) and manual wiring]
Cable Capacity Output Wires Mutual (Nom)
200 pF
Connector Type Output Terminals
WAGO 251 universal connector  [ Suitable for both automatic wiring (ALF and ADS) and manual wiring]
Wire Striplength
8.0-9.0 mm
Input Terminal Cross Section
0.50-1.00 mm²
Output Terminal Cross Section
0.50-1.00 mm²
Auto Insert (ALF/ADS) Wire Cross Section
0.5 mm²
Cable Capacity Output Wires To Earth (Nom)
200 pF
System characteristics
Rated Ballast-Lamp Power
36 W
Rated Lamp Power On TL-D
36 W
System Power On TL-D
40 W
Lamp Power On TL-D
32 W
Power Loss On TL-D
8 W
Temperature
T-Ambient (Max)
60 °C
T-Ambient (Min)
-25 °C
T-Storage (Max)
80 °C
T-Storage (Min)
-25 °C
T-Case Lifetime (Nom)
75 °C
T-Case Maximum (Max)
75 °C
T-Ignition (Max)
60 °C
T-Ignition (Min)
-25 °C
Mechanical and Housing
Housing
L360X30X28
Emergency Operation
Battery Voltage Lamp Ignition
198 V
Battery Voltage Lamp Operation
176-254
Approval and Application
Energy Efficiency Index
A2
EMI 9 kHz ... 30 MHz
EN55015
EMI 30 MHz ... 1000 MHz
EN55022 level B
Safety Standard
IEC 61347-2-3
Performance Standard
IEC 60929
Quality Standard
ISO 9000:2000
Environmental Standard
ISO 14001
Harmonic Current Emission Standard
IEC 61000-3-2
EMC Immunity Standard
IEC 61547
Vibration Standard
IEC68-2-6 F c
Bumps Standard
IEC 68-2-29 Eb
Humidity Standard
EN 61347-2-3 clause 11
Approval Marks
CE marking
ENEC certificate
VDE-EMV certificate
Temperature Marking
Yes
Emergency Standard
IEC 60598-2-22
Hum And Noise Level
Inaudible
Product Data
Full product code
871150091202230
Order product name
HF-P Xt 236 TL-D EII 220-240V 50/60Hz
EAN/UPC - Product
8711500912022
Order code
913700617866
Numerator - Quantity Per Pack
1
Numerator - Packs per outer box
12
Material Nr. (12NC)
913700617866
Net Weight (Piece)
0.400 kg
Installation Diagrams

Recently Viewed

Contact us

 

For business enquiries regarding any of our professional lighting systems.