Movement detector LRM1040 placement

  • When placing sensor consider entrances and exits to avoid going into a dark area.
  • Do not position them close to air ventilation or heating outlets – air flow can trigger the sensor.

 

Example of the 1 zone car park

  • Two sensors placed on the wall to ensure a full sensor detection converge.
  • One zone means that all illuminates will be switched on/off.
Parking decicated application bundle 3 image 1 graph and chart
Parking decicated application bundle 3 image 2 floor plan

Movement detector LRM1040 specification grid

Detecting range at 2 - 5 m heigh
12 m
Recommended mounting height

1.8 - 2.5 m (wall mounting)

2.5 - 4.0 m (ceiling mounting)

Switch off delay
5 sec. - 12 min.
Number of luminaires on one control
≤ 24