You are now visiting our Global professional lighting website, visit your local website by going to the USA website

Lighting in


ABT Car parking level progress application bundle 1


Step 6.3: Dedicated application bundle


Presence detector LRM1011 placement

  • Do not position close to air ventilation, curtains or heating outlet, as air flow can trigger motion sensor
  • Do not position too close to a door, as sensor might detect motion outside when door open
  • Extend sensor hold time In case lights switch off annoyingly whenever users are seated without moving
  • When positioning sensor, keep in mind it detects motions best when right in front of it (90 degrees)


Recommended for optimal energy saving:


3 separate groups of luminaires , each connected with 2 sensors. Each group will react separately on movement.

Detection coverage diagram
Office floor plan

Presence detector LRM1011

Detecting range at 2 - 5 m height
Ø 6 m - 11 m
Recommended mounting height
2 m - 5 m
Switch off delay
10 sec. - 30 min. in 6 steps
Number of luminaires on one control
≤ 15



Step 7: Tune your offer with TCO